Inspections by installation
RIPCI: your own staff check every three months, the maintenance company every year and an inspection body every ten
The Reglamento de instalaciones de protección contra incendios (RIPCI, the Spanish fire protection installations regulation, Royal Decree 513/2017) splits the work between three parties. The three-monthly and six-monthly checks can be done by your own staff; the yearly and five-yearly ones only by an authorised maintenance company; and every ten years, unless an exemption applies, an inspection body inspects the installation. Records are kept for at least five years.
The short answer
If your premises have fire extinguishers, equipped fire hose reels (BIE, "bocas de incendio equipadas"), detection and alarm or sprinklers, the RIPCI requires you to maintain them within maximum intervals. Every three months someone looks at the extinguisher in the corridor: that it is in its place, visible, with the seal intact and the pressure gauge needle in the operating zone. You can do that check yourselves. Every year, and every five years, an authorised maintenance company has to come in. Everything goes in writing, and the paperwork is kept for at least five years.
And every ten years the owner has to ask an inspection body to inspect the installation, unless it falls under one of the exemptions in Article 22. Since 2025 there is a new and very practical one: if all you have is fire extinguishers, fire blankets, evacuation plans or emergency lighting, that inspection does not apply to you.
What the rule says
The RIPCI sets out how active fire protection equipment is designed, installed, maintained and inspected. Its Article 21 requires the equipment to undergo the checks in Annex II, which sets for each item "el tiempo máximo que podrá transcurrir entre dos mantenimientos consecutivos" (the maximum time that may pass between two consecutive maintenance visits): an interval, not a calendar date.
Las actas de estos mantenimientos, firmadas por el personal cualificado que los ha llevado a cabo, estarán a disposición de los servicios competentes en materia de industria de la Comunidad Autónoma, al menos, durante cinco años ("The records of this maintenance, signed by the qualified staff who carried it out, shall be available to the regional industry authorities for at least five years.")
Annex II itself splits the work. The tasks in table I (every three and six months) and table III (signage) can be done by "personal especializado del fabricante, de una empresa mantenedora, o bien, por el personal del usuario o titular de la instalación" (specialist staff of the manufacturer or of a maintenance company, or the staff of the user or owner of the installation). Those in table II (every year and every five years) only by the manufacturer or the maintenance company.
A maintenance company becomes authorised by filing a responsible declaration with the regional government, which is valid indefinitely and across Spain (Art. 16). It has duties of its own (Art. 17): telling you the dates that are due, fixing the faults you ask it to fix, giving you a report on what does not work, keeping its paperwork for five years and putting a label on every extinguisher it services with its number, the date of the check and the date of the next one. An owner with the technical means, staff and liability insurance can register as a maintainer itself (Art. 14(2)).
Who it binds, and from what threshold
The RIPCI has been in force since 12 December 2017 and applies to any active fire protection installation, whether in a bar, an office or the car park of a residents' association. What it does not say is what equipment each building needs: for that it refers to the Código Técnico de la Edificación (Spanish Building Code) for buildings (Art. 19(2)) and to the industrial fire safety regulation for industrial units (Art. 19(1)).
Two thresholds are in the text. Fire extinguishers and fire blankets can be put up by the user if the premises are no larger than 100 m² or are a detached family home, and evacuation plans always can (Art. 9(2)). An installation with only that equipment needs no commissioning procedure (Art. 20(2)); the rest need the installer's certificate and a maintenance contract with an authorised maintenance company (Art. 20(1)), something that since 2025 is also required in buildings covered by the Building Code.
What is checked, how often and by whom
| Equipment | Every 3 months (owner or maintenance company) | Every 6 months (owner or maintenance company) | Every year and every 5 years (maintenance company only) |
|---|---|---|---|
| Fire extinguishers | In place and undamaged; suited to the risk; accessible and signposted; instructions legible; pressure in the operating zone; seals; not discharged | — | Yearly under standard UNE 23120; every 5 years, level C pressure test ("timbrado") |
| Fire hose reels (BIE) | Signage, access, pressure on the gauge and condition of nozzle, valve and hose | — | Yearly and five-yearly under UNE-EN 671-3; new hose at least every 20 years |
| Detection and alarm | Control panel and its indications, each power source, batteries, call-point signage, visual and audible alarms | Location, visibility and condition of the manual call points | Yearly: test of every detector and call point and of the programmed actions |
| Sprinklers and other fixed systems | Sprinklers and nozzles unobstructed, gauges, controls signposted | Pipework, valves open, power to the pumps | Yearly and every 3 years under UNE-EN 12845; 10-year and 25-year programmes |
| Water supply (tank and pumps) | Components, automatic and manual start, levels, batteries | Valves, motors, electrical supply | Yearly: water reserve, filters and supply curves |
| Luminescent signage | — | — | Yearly, and the owner may do this one (table III): presence, legibility, glow in the dark and fixings |
Source: RIPCI, Annex II, tables I, II and III, as worded by Royal Decree 164/2025.
The tables also set three service lives. A detector lasts what its manufacturer says and, if it says nothing, 10 years from commissioning; after that it is replaced or a sample is verified every five years (table II). Fire hose reel hoses are replaced at least every 20 years, unless the manufacturer certifies longer. And photoluminescent signs are replaced 20 years after manufacture, unless measuring a sample gives values of no less than 80 per cent of the factory values under table III of Annex II; that measurement is repeated every ten years.
The fire extinguisher and its twenty years
The five-yearly check on an extinguisher is a level C pressure test, the "timbrado", and the RIPCI allows it to be repeated, the "retimbrado", "por tres veces" (three times) from the date of the first test (Annex II, table II). The twenty-year limit is not written in the RIPCI: it is in the Reglamento de equipos a presión (the Spanish pressure equipment regulation).
Los extintores de incendios, como excepción, se someterán exclusivamente a las pruebas de nivel C cada cinco años […] y tendrán una vida útil de veinte años a partir de la fecha de fabricación. ("Fire extinguishers, as an exception, shall only undergo level C tests every five years […] and shall have a service life of twenty years from the date of manufacture.")
The twenty years run from manufacture, not from when you bought it or hung it on the kitchen wall. The extinguisher's inspection plate shows the date of manufacture first and then the date of each level C test (pressure equipment regulation, Annex III, section 5).
The ten-yearly inspection (Article 22)
Where no specific rule governs inspection, the owner must ask, at least every ten years, for an accredited inspection body (OCA, "organismo de control") to inspect its fire protection installations. A report is drawn up and signed by the body's technician and by the owner, and both keep a copy. If there are breaches, the body sets deadlines to put them right and, if they are very serious or are not fixed, it reports them to the regional industry authority.
It does not apply to premises in residential housing use, nor to those in administrative or educational use under 2,000 m² built, nor to those in retail, public assembly or car park use under 500 m², provided they have no high special-risk areas or rooms and no storage-use areas. Outside that list of six uses, the article gives no exemption by floor area.
Estas inspecciones tampoco serán obligatorias para aquellos lugares cuyas instalaciones consten únicamente de los equipos indicados en el artículo 20.2 o de Sistemas de alumbrado de emergencia, salvo que su reglamentación específica lo exija. ("Nor shall these inspections be mandatory where the installations consist only of the equipment in Article 20(2) or of emergency lighting systems, unless their specific regulations require it.")
The equipment in Article 20(2) is that of Article 9(2): fire extinguishers, fire blankets, evacuation plans and systems that form part of a machine. A 700 m² shop with extinguishers and emergency lighting, and nothing else, does not have the ten-yearly inspection; if it also has a fire hose reel network, it does, because it exceeds the 500 m² of retail use. For installations already in place in 2017, the first inspection fell due ten years after commissioning (fourth transitional provision).
What paperwork is kept
- Maintenance records for each task, signed by whoever did it and by the owner's representative; the maintenance company's records carry its certificate and the checklists (Annex II(5)).
- Those done by your own staff (tables I and III) need not follow the UNE 23580 formats: the minimum content of Annex II(5) and the details of the last maintenance are enough.
- Evidence of the maintenance programme: the owner and the company keep it for at least five years, up to date and available to the industry authority (Annex II(6)).
- Report of the ten-yearly inspection, signed by the inspection body and by the owner, who both keep a copy (Art. 22(3)).
- Label on every extinguisher with the company's number, the date of the check and the date of the next one (Art. 17(g)).
What the rule does not say
Worth knowing
The RIPCI does not say how many extinguishers or what equipment your premises need: it refers that to the Building Code or to the industrial regulation. It does not say "twenty years" of extinguisher life: that comes from the pressure equipment regulation. And it sets no periodic test of emergency lighting: it requires it to be maintained under the Reglamento electrotécnico para baja tensión (the low-voltage electrical regulation) (Annex II(8)), which has its own inspection.
Nor does it say the three-monthly check has to be done by a company: you can do it yourselves, as long as it is put in writing. And the fact that the maintenance company must tell you the dates (Art. 17(f)) does not remove your own duty to keep evidence of the maintenance (Annex II(6)).
If it is an industrial unit
In an industrial establishment the inspection is not the one in Article 22: it is governed by the industrial fire safety regulation, which since 10 May 2025 is the one in Royal Decree 164/2025 (the one in Royal Decree 2267/2004 has been repealed). Its Article 13 requires the owner to ask an inspection body for an inspection at least every five years, whatever the intrinsic risk level; under the previous regulation it was five, three or two years depending on whether the risk was low, medium or high.
Units that were already operating hold their next inspection within the deadline set in their last report and then move to five years (fifth transitional provision); equipment maintenance is still that of the RIPCI (Art. 12(2)). You have the full picture, with the exemptions for small units, in regulations for industrial units.
Does it depend on the region?
The regulation is national and basic, but the regional governments apply it: companies' declarations and installation certificates are filed with their industry department, and their inspection services are the ones who ask for the records. The ten-yearly inspection can follow standard UNE 192005-2 "o bien, el protocolo equivalente que cada comunidad autónoma tenga establecido" (or the equivalent protocol each region has set up) (Art. 22(1)). If your building also needs a self-protection plan, that is decided by a different rule altogether.
Frequently asked questions
How often must fire extinguishers be checked in Spain?
Every three months, a check your own staff can do: that it is in place, signposted, with its seal and the pressure in the operating zone. Every year, the maintenance under standard UNE 23120, and every five years, the level C pressure test or "timbrado"; those two can only be done by an authorised maintenance company. Tables I and II of Annex II of the RIPCI say so.
Can I check the extinguishers myself without hiring anyone?
The three-monthly and six-monthly checks, yes: Annex II of the RIPCI allows the user's or owner's staff to do them, with a record signed by whoever did it and by the owner. The yearly and five-yearly ones, no: only the manufacturer or a maintenance company authorised by the regional government. If the owner wants to do them, it has to register as a maintainer itself (Article 14(2)).
How many years does a fire extinguisher last?
Twenty years from its date of manufacture. That is not in the RIPCI but in the pressure equipment regulation (Royal Decree 809/2021, Annex III, note 1), which adds that it will undergo the level C test every five years at the hands of an authorised maintenance company. The RIPCI, for its part, allows re-testing "por tres veces" (three times) from the date of the first test.
How often is the fire protection inspection required?
At least every ten years, and the owner requests it from an inspection body (Article 22 of the RIPCI). It does not apply to residential housing use, to administrative or educational use under 2,000 m², or to retail, public assembly or car park use under 500 m², with no high special-risk or storage areas. Since 2025 it also does not apply if all you have is extinguishers, blankets, evacuation plans or emergency lighting.
How long must maintenance records be kept?
At least five years. Article 21(2) of the RIPCI says the records, signed by whoever did the maintenance, shall be available to the regional industry authority for five years from issue, and Annex II(6) requires both the company and the owner to keep that evidence, with entries kept up to date.
Does an industrial unit have the ten-yearly inspection?
No. Inspection of an industrial unit is governed by the industrial fire safety regulation, which since May 2025 is the one in Royal Decree 164/2025. Its Article 13 sets it at least every five years, by an inspection body, for any intrinsic risk level. Existing units hold the next one within the deadline set in their last report and then move to five years.
Where it usually applies
- Restaurants and barsThe obligations of a restaurant or a bar in Spain: what is specific to the kitchen and the checks on the premises, each with the condition that triggers it, how often it applies and its article.
- GymsA gym: no national law; qualifications, insurance and notices under each region's sports professions act, plus low voltage, Legionella, pool, RIPCI and defibrillator as premises.
- HotelsA hotel: guest register and reporting within 24 hours, regional classification, low voltage and lift as a public-assembly venue, RIPCI, Legionella, pool, kitchen and defibrillator.
- Residents' associationsThe obligations of a Spanish residents' association: upkeep, reserve fund, owners' meeting and administrator under the Horizontal Property Act, building logbook, building inspection and the checks on each communal installation.
- Shops and franchisesA shop: responsible declaration up to 750 m², opening hours, prices, franchises with no register since 2018, complaint forms, accessibility adjustments and the inspections of premises open to the public.
- OfficesThe obligations of an office in Spain: temperature and upkeep of the premises, screen work, health and safety, coordination with contractors, internal reporting channel, right to disconnect and building checks.
- SchoolsA school: minimum facilities, protocols against violence and a wellbeing coordinator, canteen and menus from April 2026, self-protection and the building inspections.
- Industrial unitsAn industrial unit: fire inspection every five years under the 2025 regulation, chemical storage (APQ), air receivers, work equipment, low voltage, cooling towers and self-protection.
Other mandatory inspections
- Self-protection planWho needs a self-protection plan under the Basic Directive in force since 11 October 2026, what it contains, how often it is reviewed and what the regions add.
- Low-voltage inspectionInspection by an accredited body every 5 years for the premises in ITC-BT-05 (bars, restaurants and hotels always) and every 10 years for residential common areas over 100 kW.
- Thermal installations (RITE)Maintenance company from 5 kW; contract, annual certificate and efficiency inspection every 4 years above 70 kW, with the minimum intervals of table 3.1.
- LegionellaWhat Royal Decree 487/2022 requires of the holder of business premises: a control plan, hot water temperatures, yearly disinfection, Legionella sampling and records kept for five years.
- Lift inspectionWhat ITC AEM 1 (Royal Decree 355/2024) requires of a lift's holder: a contract with a lift maintenance company, monthly servicing, a periodic inspection every 2, 4 or 6 years and deadlines for defects.
- Swimming poolsWhat Royal Decree 742/2013 requires by type of pool: self-monitoring, daily and monthly checks, information for users and incidents, and what it leaves to the autonomous communities.
- HACCP (APPCC)What Article 5 of Regulation 852/2004 requires of a bar, a restaurant or an institutional kitchen in Spain: the seven principles, the records, the flexibility and what is no longer in force.
- Defibrillator (AED)What the Spanish national rule on defibrillators requires, and who must have one in Madrid, Catalonia, Andalusia and the Basque Country, with each threshold and article.